| Model | Champ TW 6K | Champ TW 10K | ||
| Capacity | 6000 VA / 5400W | 10000 VA / 9000W | ||
| Input Voltage Range | 110-300 VAC (50% load), 176-300VAC (100% load) | |||
| Input Frequency | 46Hz ~ 54Hz or 56Hz ~ 64Hz | |||
| Power Factor | ≥ 0.99 @ Nominal Voltage (100% load) | |||
| Output Voltage | 208/220/230/240 VAC | |||
| Output Frequency Range | 46Hz ~ 54Hz or 56Hz ~ 64Hz | |||
| Current Crest Ratio | 3:1 | |||
| Harmonic Distortion | ≤ 3 % THD (Linear Load) ≤ 5 % THD (Non-linear Load) | |||
| Output Transfer Time (Typical) | Zero (AC to DC) Zero (Inverter to Bypass) | |||
| Output Waveform (Batt. Mode) | Pure Sinewave | |||
| Battery Type & Number | No internal battery | No internal battery | ||
| Backup Time | Up to 12mins @ full load | Up to 6mins @ full load | ||
| Typical Recharge Time (up to 90% capacity) | 4 hours | |||
| Indicators / AC Mode | ✔ | |||
| Indicators / Battery Mode | ✔ | |||
| Indicators / Battery level | ✔ | |||
| Indicators / Load level | ✔ | |||
| Indicators / Bypass mode | ✔ | |||
| Indicators / Fault | ✔ | |||
| Alarm / Battery Mode | Sounding every 4 seconds | |||
| Alarm / Low Battery | Sounding every second (Batt. Mode) | |||
| Alarm / Overload | Sounding twice per second | |||
| Alarm / Fault | Continuously sounding | |||
| Physical Dimension (mm) | 369 x 190 x 318 (DxWxH) | 442 x 190 x 318 (DxWxH) | ||
| UPS Net Weight (kg) Long run time Model | 12 | 16 | ||
| Operating Environment / Humidity | 20-90 % RH @ 0- 40°C (non-condensing) | |||
| Operating Environment / Noise Level | Less than 50dB @ 1 Meter | |||
| Management / Optional USB / RS-232 Port | Supports Windows® 98/XP/2000/Vista/7/8/10, Windows® Server 2000/2003/2008/2012/2016, Linux, and MAC | Supports Windows® 98/XP/2000/Vista/7/8/10, Windows® Server 2000/2003/2008/2012/2016, Linux, and MAC | ||
| Optional SNMP | Power management from SNMP manager and web browser | |||